Installing Vertical Blade Aluminum Dampers
Contact TAMCO Customer Service for configurations not shown.
ONE-SECTION
VERTICAL BLADE DAMPER
TWO-SECTION
VERTICAL BLADE DAMPER
  • Single-section vertical blade dampers must be installed so that linkage is at the top.
  • The actuator must be mounted on the drive rod which extends beyond the bottom of the damper
  • Multiple sections cannot be linked. Actuators must be connected to each section
  • The base of the damper must be extremely well supported.
  • The customer must specify that the damper will be installed in a vertical position. Our production software will adjust the configuration automatically.
  • There is no predetermined maximum blade length. Contact the factory for details.
  • TAMCO will honor its warranty if all of the above instructions are adhered to at the time of order and installation.

Products | Options | Accessories | Technical Data | Installation Guidelines
Product Schedules | Representatives | About Us | Contact Us
© 2012 T. A. Morrison & Co. Inc. All rights reserved.