Torque Requirements
Series 1000 / 1000 SW / 1500 / 1500 SW
9000 / 9000 SC / 9000 SW / 9000 BF / 9000 ECT
Note: Tested dampers are “Flanged to Duct” type.
SEALING TORQUE (in.-lbs.)
up to 2 in. and 1000 fpm face velocity
Values in Sealing Torque chart (left) reflect the maximum torque requirements up to 2 in. w.g. and/or 1000 fpm face velocity. Refer to Velocity or Pressure Torque charts (below) if system design surpasses criteria of Sealing Torque chart. Base torque requirements on the greatest value obtained.
VELOCITY TORQUE (in.-lbs.)
at 1000 fpm face velocity
Multiply value in Velocity Torque chart by the multiplier listed below to obtain torque for greater design face velocity.
PRESSURE TORQUE (in.-lbs.)
at 2 in. w.g. differential
Multiply value in Pressure Torque chart by the multiplier listed below to obtain torque for greater design pressure.
NOTE :
Refer to Blade Design Pressure Limitations to ensure that the damper is within the stated design limits in respect to maximum static pressure. (See Series 9000 BF/9000 ECT/9000/9000 SC/1500/1000 literature.)